Limited A1140-DC is available at low cost from stock - click here to purchase for next day delivery

ABB A43 213-100 Three Phase 80A Direct Connected MID Meter with Pulse and M-Bus Output (2CMA170523R1000)

ABB A43 213-100 Three Phase 80A Direct Connected MID Meter with Pulse and M-Bus Output (2CMA170523R1000)

£265.73

£318.88 inc. VAT

Product Description

ABB A43 213-100 Three Phase Direct Connect meter is MID certified and has the option of Modbus output via RS485. It is suitable for most of the common applications for reliable metering of energy use.

Specification

Voltage/Current Inputs

Nominal voltage

3 x 230/400 V AC

Voltage range

3 x 57.7/100 ... 288 /500 V AC (-20% - +15%)

Power dissipation voltage circuits

0.8 VA (0.8 W) total

Power dissipation current circuits

0.007 VA (0.007 W) per phase at 230 V AC and Ib

Base current Ib

5 A

Rated current In

-

Reference current Iref

5 A

Transitional current Itr

0.5 A

Maximum current Imax

80 A

Minimum current Imin

0.25 A

Starting current Ist

< 20 mA

Terminal wire area

1 - 25 mm²

Recommended tightening torque

3 Nm

General Data

Frequency

50 or 60 Hz ± 5%

Accuracy Class

A (CL 2), B (CL 1)
Active energy1%, 2%

Display of energy

Pixel oriented

Environmental

Operating temperature

40°C - +70°C

Storage temperature

40°C - +85°C

Humidity

75% yearly average, 95% on 30 days/year

Resistance to fire and heat

Terminal 960 °C, cover 650°C (IEC 60695-2-1)

Resistance to water and dust

IP20 on terminal block without protective enclosure and IP51 in a protective enclosure, according to IEC 60529

Mechanical environment

Class M2 in accordance with the Measuring Instrument Directive (MID). (2004/22/EC)

Electromagnetic environment

Class E2 in accordance with the Measuring Instrument Directive (MID), (2004/22/EC)

Outputs

Current

2 - 100 mA

Voltage

5 - 40 V DC

Pulse output frequency

Programmable: 1 - 999999 imp/kWh

Pulse length

Programmable: 10 - 990 ms

Terminal wire area

0.5 - 1 mm²

Recommended tightening torque

0.25 Nm

EMC Compatibility

Standards

IEC 62052-11, IEC 62053-21 class 1 & 2, IEC 62054-21, GB/T 17215.211-2006, GB/T 17215.321-2008 class 1 & 2, GB 4208-2008, EN 50470-1, EN 50470-3 category A and B.

Mechanical

Material

Polycarbonate in transparent front glass, bottom case, upper case and terminal cover.
Glass-reinforced polycarbonate in polycarbonate in terminal cover.

Dimensions

Width

123 mm

Height

97 mm

Depth

65 mm

DIN Modules

7

Downloads

Ask an expert about the
ABB A43 213-100 Three Phase 80A Direct Connected MID Meter with Pulse and M-Bus Output (2CMA170523R1000)

Help & Advice

Knowledge Base

Knowledge Base

Our Knowledge Base section provides in-depth guides on metering related topics, and can aid you in the process of buying the right product.

Find out more

Our Products

addressarrow-leftcaret-downcaret-leftcaret-rightmenuorderpadlockpdf