*A1140-DC meters available from stock @ £70.00! *

Carlo Gavazzi EM111 Single Phase MID Energy Analyzer with Modbus RS485 Port (EM111-DIN.AV8.1.X.S1.PFB)

Carlo Gavazzi EM111 Single Phase MID Energy Analyzer with Modbus RS485 Port (EM111-DIN.AV8.1.X.S1.PFB)

£71.74

£86.09 inc. VAT

Product Description

Carlo Gavazzi's EM111 range of meters are suitable for active energy metering and cost applications up to 45A with dual tariff management availability. Housed in 1-DIN module fashion, the meter's small and compact design makes it ideal for quick installation.

Product Features:
  • Class 1 (kWh) according to EN62053-21
  • Class B (kWh) according to EN50470-3
  • Accuracy ±0.5% RDG (current/voltage)
  • Energy measurement: kWh and kvarh (imported/exported); kWh+ by 2 tariffs
  • System variables, kW, kvar, V, A, PF, Hz, kWdmd, kWdmd peak
  • Energy readout on display: 7 digit
  • Variable readout on display: 4 digit
  • MID Certified
  • Direct current measurement up to 45AAC
  • Self power supply
  • Modbus port

Specification

Rated Inputs

Current type

1-phase loads, direct
connection

Current rate

5(45)A

Nominal voltage

230VLN AC (AV8 option), 120 VLN (AV7 option)

Accuracy (@25°C ±5°C, R.H. ≤60%, 45 to 65 Hz)

AV1

Imin=0.25A

Ib: 5A

Imax: 45A

Un: 120VLN -30% +30%

AV0

Imin=0.25A

Ib: 5A

Imax: 45A

Un: 230VLN -30% +20%

Active energy

Class 1 according to EN62053-21, and MID Annex MI-003 Class B (Class B (kWh) according to EN50470-3)

Reactive energy

Class 2 according to EN62053-23

Start-up current

20mA (AV7, AV8),
-20mA (AV7, AV8) positive or negative Self-consumption is not measured.

Start-up voltage

84VLN (AV7), 161VLN (AV8)

Overloads

Current

Continuous: 45A, @ 50Hz
For 10ms: 1350 A

Voltage

Continuous: 1.2 Un
For 500ms: 2Un

General

Sampling rate

4096 samples/s @ 50Hz

4096 samples/s @ 60Hz

Operating temperature

-25 to +65 °C, indoor, (R.H. from 0 to 90% non- condensing @ 40°C)

Storage temperature

-30°C to +80°C (R.H. < 90% noncondensing @ 40°C)

Overvoltage category

Cat. III

Temperature drift

≤200ppm/°C

Standard

Safety: EN62052-11
Metrology: EN62053-21, EN50470-3

Approvals

CE, MID (PF option only)

Mechanical

Connections

Cable cross-section area: Measuring inputs: max. 6 mm² with/without metallic cable ferrule; Max. screw tightening torque: 1.1 Nm
Other Terminals: 1.5 mm², Min./Max. screws tightening torque: 0.4 Nm

Dimensions (W x H x D)

17.5 x 91.5 x 63 mm

Material

Noryl, self-extinguishing: UL 94 V-0

Sealing covers

Included

Mounting

DIN-rail

Protection degree

Front: IP51
Screw terminals (cable inputs):
IP20

Weight

Approx. 80 g (packing included)

Power Supply

Self power supply

AV8: 230VAC VL-N, -30% +20% 45 to 65 Hz

AV7: 120VAC VL-N, -30% +30% 45 to 65 Hz

Power consumption

≤ 1.0W, ≤ 8VA

Downloads

Ask an expert about the
Carlo Gavazzi EM111

Help & Advice

Knowledge Base

Knowledge Base

Our Knowledge Base section provides in-depth guides on metering related topics, and can aid you in the process of buying the right product.